Table 4- 26 Technical data of the PM240-2, FSE (400 V)
Line voltage 3-phase 380 … 480 V AC -20/+10 %
Article No.
without integrated line filter
with internal line filter
6SL3210–
1PE28-8UL0
1PE28-8AL0
6SL3210–
1PE31-1UL0
1PE31-1AL0
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
s6
max
A
A
A
90
75
108
110
90
132
1)
on basis of I
n
kW
45
55
Rated pulse frequency
Max. Pulse frequency
kHz
4
4
2)
of the external braking
Ω ≥ 8.2 ≥ 8.2
Max. Cable length
to the braking resistor
Line supply connection L1, L2, L3, PE
Screw-type terminal
Torx M8
Conductor cross section. 25 … 70 mm
2
Tightening torque: 8.0 … 10 Nm
Motor connection U2, V2, W2, PE
DCP, DCN
Connection for braking resistor
R1, R2 Screw-type terminal
Torx M5
Conductor cross section. 16 … 35 mm
2
Tightening torque: 2.5 … 4.5 Nm
3)
Without line filter
kg
26
26
Rated output of a typical standard induction motor at 400 V.
The input current depends on the motor load and line impedance. The input curr
ents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
To observe the limit values of EN 61800-3 category C2, for Power Modules PM240-2 with integrated line filter 150 m
(shielded) it the max. motor cable length.