A.8.3
SINAMICS V60 faults and alarms
A.8.3.1
Overview
Alarm code
Description
A01
Unable to identify the power board
A02
Parameter validation error (CRC error, encoder type or parameter header invalid)
A03
Unable to write data to memory
A04
Control voltage is lower than 3.5 V.
A05
IGBT is detected overcurrent.
A06
Internal chip is detected overcurrent.
A07
Grounding short circuit occurs during drive initialization
A08
Signals from encoder phases U, V, W are detected all the same (all high or all low)
A09
TTL pulse error
A14
Software failure
A21
DC link voltage is higher than 405 V
A22
IGBT current exceeds the upper limit for 300 ms
A23
DC link voltage is lower than 200 V
A24 The difference between the position setpoint and the position actual value is greater than 1000 pulses
(1/10 rotation).
A41
Actual motor speeds is higher than 2300 rpm
A42
IGBT becomes overheating
A43
Following error exceeds the limit
A44
Motor load exceeds nominal motor torque
A45
Enable signal from Terminal 65 is lost during normal drive running
A.8.3.2
Common faults and alarms
Alarm
code
Background
Possible Cause
Remedy
A01
Power board is broken
Replace the drive with a new one
A02 The memory is damaged due to unexpected
power-off during data saving
Restore default parameters
A03
Memory is damaged
Replace the drive with a new one
A04
The 24 V DC supply is abnormal
Check the 24 V DC supply
The drive is defective
Replace the drive with a new one
A05 This alarm may occur
when the DC link is
connected
• There is a short-circuit between terminals
U, V, W and PE on the drive
• Bad grounding
• Motor insulation is broken
• The drive is broken
• Check the wiring
• Make a correct grounding
• Replace the motor with a new
one
• Replace the drive with a new
one
This alarm may occur
when the motor is run-
ning
A06 This alarm may occur
when the DC link is
connected
•
There is a short-circuit between terminals
U, V, W and PE on the drive
• Bad grounding
• Motor insulation is broken
• The drive is broken
•
Check the wiring or whether
the connection to U, V or W is
broken
• Make a correct grounding
• Replace the motor with a new
one
• Replace the drive with a new
one
This alarm may occur
when the motor is run-
ning

Table of Contents

Other manuals for Siemens SINUMERIK 808D ADVANCED

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK 808D ADVANCED and is the answer not in the manual?

Siemens SINUMERIK 808D ADVANCED Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK 808D ADVANCED
CategoryControl Unit
LanguageEnglish

Related product manuals