NC Commissioning with HMI Advanced
11.7 Digital and analog I/O devices
Manual
476 Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
ADI4
The high byte of the input word (slot 21)
MD10366 $MN_HW_ASSIGN_DIG_FASTIN[3] = H050010E7 (4327
D
)
Hardware assignment: output bytes
The following output bytes are used by the NC:
ET 200
The 1st output byte of the output modules (slots 4 and 5)
MD10368 $MN_HW_ASSIGN_DIG_FASTOUT[0] = H05000080 (128
D
)
MD10368 $MN_HW_ASSIGN_DIG_FASTOUT[1] = H05000082 (130
D
)
ADI4
Both output bytes of the output word (slot 22)
MD10366 $MN_HW_ASSIGN_DIG_FASTOUT[2] = H050010E6 (4326
D
)
MD10366 $MN_HW_ASSIGN_DIG_FASTOUT[3] = H050010E7 (4327
D
)
Machine data
Table 11-54 Digital and analog I/Os: Machine data
Number Name Name
General ($MN_ ... )
10300 FASTIO_ANA_NUM_INPUTS Number of active analog NC inputs
10310 FASTIO_ANA_NUM_OUTPUTS Number of active analog NC outputs
10320 FASTIO_ANA_INPUT_WEIGHT Weighting factor for analog NC inputs
10330 FASTIO_ANA_OUTPUT_WEIGHT Weighting factor for analog NC outputs
10350 FASTIO_DIG_NUM_INPUTS Number of active digital NC input bytes
10360 FASTIO_DIG_NUM_OUTPUTS Number of active digital NC output bytes
10362 HW_ASSIGN_ANA_FASTIN Hardware assignment of external analog NC inputs
10364 HW_ASSIGN_ANA_FASTOUT Hardware assignment of external analog NC outputs
10366 HW_ASSIGN_DIG_FASTIN Hardware assignment of external digital NC inputs
10368 HW_ASSIGN_DIG_FASTOUT Hardware assignment of external digital NC outputs
10380 HW_UPDATE_RATE_FASTIO Update rate of clock-synchronous external NC I/Os
10382 HW_LEAD_TIME_FASTIO Rate time for clock-synchronous external NC I/Os
10384 HW_CLOCKED_MODULE_MASK Clock-synchronous processing of external NC I/Os
10394 PLCIO_NUM_BYTES_IN Number of directly readable input bytes of the PLC I/Os
10395 PLCIO_LOGIC_ADDRESS_IN Start address of the directly readable input bytes of the PLC
I/Os
10396 PLCIO_NUM_BYTES_OUT Number of directly writeable output bytes of the PLC I/Os
10397 PLCIO_LOGIC_ADDRESS_OUT Start address of the directly writable
output bytes of the PLC I/Os