NC Commissioning with HMI Advanced
11.11 NC/PLC Diagnosis
Manual
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
491
Group: settings
The following functions are grouped together via the "Settings" group box:
Signal input for shutdown behavior: Signal source
This selection field is for configuring the digital input used for the shutdown signal of the
UPS:
Disabled
No input signal is present.
NC input 0...3
The shutdown signal of the UPS is connected to the configured digital input of the MCI
board extension module (Chapter
"Interface description" (Page 60)).
Signal input for shutdown behavior: Signal level
This selection field is for configuring the level of the shutdown signal of the UPS:
Low active
Upon detection of the low level (0) at the configured input, first the SINUMERIK 840Di
sl NC / PLC and then Windows XP are closed.
High active
Upon detection of the high level (1) at the configured input, first the SINUMERIK 840Di
sl NC / PLC and then Windows XP are closed.