Communications 9810 series - User manual
101 7EN05-0390-08
8. Configure the connection type:
Connection type Configuration
Serial connection
Select the serial communications port that is connected to the
Modbus server devices from the Assigned Port list.
TCP connection
Enter the IP address of the Modbus server device, making
sure that the IP port is set to 502.
Make sure that the Modbus RTU and Modbus TCP/IP
protocols are enabled.
9. Click OK to return to the Modbus Device dialog.
10. Click OK to add the server device. The device now appears on the list.
11. Repeat steps 4 through 10 to add all your Modbus server devices.
Your meter as a Modbus server
Your meter as a Modbus server over Ethernet
Your meter can function as a Modbus server over Ethernet.
A Modbus client
B Ethernet Modbus TCP
C Your meter
Your meter does not require any Modbus-specific configuration to act as a Modbus server device
over Ethernet.
Your meter as a Modbus server on a serial network
Your meter can function as a Modbus server on a serial network.