Logging 9810 series - User manual
225 7EN05-0390-08
4-30 10s Freq (Data Rec 21)
Power Frequency PqFlag 10s
4-30 Intrp Log (Data Rec 22)
V Intrp DrtnAll (voltage interruption duration - all voltages)
For more information, see the IEC 61000-4-30 compliance and ION meters technical note,
available on www.usa.siemens.com/pds.
IEEE 519 compliance logs
The IEEE 519 compliance logs are used to record IEEE 519 compliance parameters:
Data recorder Description
519 Hrm I-X (Data Rec 35)
Current harmonics statistics and counters:
Weekly 95th percentile 10 min intervals
519 Hrm I-Y (Data Rec 36)
Current harmonics statistics and counters:
Weekly 99th percentile 10 min intervals
519 Hrm I-Z (Data Rec 14)
Current harmonics statistics and counters:
Daily 99th percentile 3 s intervals
519 Hrm V-X (Data Rec 42)
Voltage harmonics statistics and counters:
Weekly 95th percentile 10 min intervals
519 Hrm V-Z (Data Rec 13)
Voltage harmonics statistics and counters:
Daily 99th percentile 3 s intervals
I1 Hrm 1-16 (Data Rec 44) I1 current harmonics - 10 min
I1 Hrm 17-32 (Data Rec 50) I1 current harmonics - 10 min
I1 Hrm 33-48 (Data Rec 56) I1 current harmonics - 10 min
I2 Hrm 1-16 (Data Rec 45) I2 current harmonics - 10 min
I2 Hrm 17-32 (Data Rec 51) I2 current harmonics - 10 min
I2 Hrm 33-48 (Data Rec 57) I2 current harmonics - 10 min
I3 Hrm 1-16 (Data Rec 46) I3 current harmonics - 10 min
I3 Hrm 17-32 (Data Rec 52) I3 current harmonics - 10 min
I3 Hrm 33-48 (Data Rec 58) I3 current harmonics - 10 min
V/I Hrm 49-50 (Data Rec 59) V1, V2, V3, I1, I2, I3 harmonics - 10 min
V1 Hrm 1-16 (Data Rec 40) V1 voltage harmonics - 10 min
V1 Hrm 17-32 (Data Rec 47) V1 voltage harmonics - 10 min
V1 Hrm 33-48 (Data Rec 53) V1 voltage harmonics - 10 min
V2 Hrm 1-16 (Data Rec 41) V2 voltage harmonics - 10 min