Logging 9810 series - User manual
231 7EN05-0390-08
implemented before older entries are overwritten. This feature can assist in ensuring that event
log entries are not overwritten before they can be reviewed. Use ION Setup to select a user to be
the designated reader.
1. Open ION Setup.
2. Ctrl + click on the meter to select it. This switches ION Setup to Advanced mode.
3. Open the EventLogCtl Modules folder and double click EventLogCtl.
4. Enter login credentials as necessary.
5. Click the Setup Registers tab.
6. Select Designated Reader and click Edit.
7. Set Designated Reader to the user that reviews the event log (USER0 - USER50) and click
OK.
Syslog
Syslog uses the User Datagram Protocol (UDP) to transport event log information from the meter
directly to a centralized syslog server.
The syslog server can receive logs from multiple devices, including meters, then store and filter
the log information as needed. You can use ION Setup to modify the syslog network settings for
your device. Syslog is a useful feature to help maintain meter log information for extended periods
of time.
NOTE: Ethernet is required to use the syslog feature.
Syslog is an open standard allowing you to use any one of a number of syslog server applications
currently available. The decision regarding which syslog server solution to use can be based on
budget and your technical requirements. See the individual syslog server’s documentation for
more information.
Configuring Syslog network settings using ION Setup
To configure Syslog network settings using ION Setup:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Communications > Advanced Ethernet > SysLog.
4. Select Enable Syslog and click Edit.
5. Select Yes to enable the syslog server feature or select No to disable it.
6. Click OK.
7. Select Syslog Server and click Edit.
8. Enter the IPv4 address or an IPv6 address for the syslog server.
NOTE: You must enter the IP address for the syslog server, not the server’s fully-qualified
domain name.