9. Click Finish.
You are returned to the Transient Logging screen and the entry shows your new
configuration.
If nothing happens when you click Finish, check the log depths and buffer depths for all your
other data logs to make sure that the meter has enough memory for these changes. Adjust
the log depth and buffer depth of the data and waveform recorders if needed.
Configuring Advanced Power Quality
Use ION Setup to configure your meter’s power quality monitoring and logging settings for IEC
61000-4-30, EN 50160, IEEE 519, and Rapid Voltage Change (RVC).
Prerequisites and notes
Ensure that Sag/Swell alarming is enabled and configured. For details on how to setup Sag/Swell
alarming, see "Configuring sag/swell alarms using ION Setup" on page 186.
NOTE: IEC 61000-4-30 must be enabled before configuring EN 50160 or IEEE 519 logging.
NOTICE
DATA LOSS
Failure to follow these instructions can result in data loss.
Enable Sag/Swell alarming before configuring power quality disturbance related features.
Enable IEC 61000-4-30 before enabling other power quality monitoring and recording
features.
To configure Advanced Power Quality:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Power Quality > Advanced PQ.
4. Configure IEC 61000-4-30.
5. (Optional) Configure EN 50160.
6. (Optional) Configure IEEE 519.
7. (Optional) Configure RVC.
Configuring IEC 61000-4-30
To configure IEC 61000-4-30:
1. Select 4-30 Enable.
2. Click Edit to configure your meter’s IEC 61000-4-30 logging parameters.
9810 series - User manual Power quality
7EN05-0390-08 200