Inputs/Outputs 9810 series - User manual
137 7EN05-0390-08
Parameter Value/range Description
Input Mode
Pulse, KYZ, A/C,
IRIG-B*
Specifies how the meter processes the signal:
Pulse: the meter counts an entire pulse (from
off-on to on-off) as one input.
KYZ: the meter counts a transition (from off-on
or from on-off) as one input.
A/C: the meter detects analog signals where the
ON condition is based on the presence of an AC
signal.
IRIG-B*: the meter detects an IRIG-B time
synchronization signal.
Polarity Inverting/Non-Inverting
Specifies if the signal from the digital port is inverted
or not inverted.
Debounce 0.000–1.000
Specifies how long (in seconds) the signal must
remain in a state to be considered a valid state
change.
Assigned Port
Defined by your meter’s
hardware
Your meter’s physical digital input port.
EventLog Mode Log Off/Log On Specifies if events generate log entries.
State OFF/ON Indicates the status of the digital input.
* You must also configure your meter’s clock to use IRIG-B time synchronization.
Configuring option module digital inputs using ION Setup
You can configure option module digital inputs using ION Setup.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Expansion Modules > Option I/O Modules and select the module tab that
corresponds to the option module with the digital input you want to configure.
4. Select the digital input channel and click Edit.
The setup screen for that digital input is displayed.
5. Configure the digital input by selecting the parameter and clicking Edit.
6. Once the parameter has been configured, click OK to save the setting to the meter.