Commissioning
Factory default settings
Use these default values the first time you connect to your meter.
Parameter Default value
Username to log onto meter webpages USER1
Password to log onto meter webpages or access display 0
IP address
1
169.254.0.10
Subnet mask 255.255.0.0
Gateway 0.0.0.0
RS-485
COM1 Unit ID: 100
COM4 Unit ID: 103
Language English
1
The IPv6 link local address can also be used. See Self-discovery over Ethernet for details.
Commissioning using ION Setup
Use ION Setup to commission the meter for integration into your energy management system.
Connect to your meter using ION Setup then use the Setup Assistant to configure the meter.
Setup parameters are arranged in logical groupings and category folders.
Before exiting the Setup Assistant, ION Setup performs a meter configuration test and displays
the results. You can review the results and make changes as needed.
To turn off the meter configuration test:
1. Click Tools > Options.
2. Click the Assistant tab and clear the Configuration Checklist check box.
NOTE: ION Setup also performs a configuration test and displays results when configuring
certain features such as the Sag/Swell or Transient Logging wizard in the Power Quality setup
assistant.
Configuring metering parameters
Use ION Setup to configure the meter’s metering functionality.
9810 series - User manual Installation and commissioning
7EN05-0390-08 67