Alarms and alerts 9810 series - User manual
181 7EN05-0390-08
Alarm Alarm icon Alarm icon flash Alarm LED Display
Active medium
Yellow solid
bell
Flash if not
acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
Active low Blue solid bell
Flash if not
acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
Historic high
Red outline
bell
Flash if not
acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
Historic medium
Yellow outline
bell
Flash if not
acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
Historic low Gray solid bell No flash Off No flash
No active or
unacknowledged
alarms
Gray solid bell No flash Off No flash
If there are multiple active alarms, the alarm condition associated with the highest priority is
displayed. If there are multiple unacknowledged historic alarms, the meter displays the alarm
condition associated with the highest priority unacknowledged historic alarm.
NOTE: To stop an alarm from being displayed without impacting other metering features, set the
alarm priority to Info Only.
Default alarms
Your meter comes with default alarms. Some alarms are enabled by default.
NOTE: Some alarms require configuration to operate.
Name Priority Description Default
Current Sag Ph1 - 3 High Current sag alarms for phase 1, 2, 3 Disabled
Current Swell Ph1 - 3 High
Current swell alarms for phase 1, 2,
3
Disabled
Sag/Swell High Voltage sag/swell alarm Disabled