Resets 9810 series - User manual
261 7EN05-0390-08
3. Click Reset for the values you want to clear.
Parameter Description
Master Reset
Clears all cumulative and derived quantities from the
meter, including: demand, peak demand, energy,
revenue, and test mode parameters.
Clears meter event and waveform logs.
Clears COMTRADE waveform records stored in the
meter’s internal SFTP site.
Clears meter data logs.
Peak Demand Reset
Clears meter peak demand values.
NOTE: The peak demand reset has a lockout period that sets
the minimum time allowed between consecutive resets.
Min/Max Reset
Clears all accumulated maximum and minimum values stored
in the meter.
Digital Input Count Reset Clears the digital input status change counters.
Harmonics Min/Max
Reset
Clears all accumulated maximum and minimum harmonics
values stored in the meter.
Disturbance Count Reset
Clears the sag/swell event counter. The sag/swell event
counter counts the number of sag/swells that have occurred
since power-up or the last reset to provide power quality
information to energy management systems.
EN50160 Reset
Clears all EN50160 parameters and statistics accumulated in
the meter.
Performing resets using the display
You can reset the meter using the display.
Revenue-locked meters must be unlocked to perform resets that impact revenue data.
Your meter’s digital and analog outputs may change state or may not function during resets.
WARNING
UNINTENDED OPERATION
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Do not use this device for critical control or protection of persons, animals, property, or
equipment.
Meter resets clear the meter’s onboard data logs and related information.