To reset the meter using ION Setup:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Verification.
4. Select Normal Mode and click Display.
5. Select the desired tab in the Normal Mode dialog box. Depending on the tab selected,
different resets are available.
Tab Reset available
Energy Master Reset
Rolling Demand
Peak Reset
Master Reset
Volts, Amps and Power Master Reset
Conditional Energy
Cnd Reset
Master Reset
Input Metering
IM(n) Reset
NOTE: n is the input metering number, for example IM1.
6. Click the appropriate button to perform the reset. For some resets, the meter indicates that
the reset is in progress.
NOTE: Do not configure or power down your meter until it indicates that the reset is
complete or some parameters may not be completely reset.
Performing resets using the meter webpages
You can reset the meter using the meter webpages.
Meter resets clear the meter’s onboard data logs and related information.
NOTICE
DATALOSS
Failure to follow these instructions can result in data loss.
Ensure all important data from the device has been retrieved before performing a reset.
To reset the meter using the meter webpages:
1. Connect to your meter’s webpages.
2. Browse to Control > Resets.