9810 specifications 9810 series - User manual
291 7EN05-0390-08
9810 specifications
This section provides additional specifications for your meter and accessories.
NOTE: The information contained in this section is subject to change without notice. You can
download updated documentation from www.usa.siemens.com/pds or contact your local
Siemens Industry representative for the latest updates.
Mechanical characteristics
Mounting options
DIN rail: IEC 60715 (DIN EN 60715), TH 35–7.5 or TH 35–15
Panel mount: with 9810BBADAPTER
Orientation Vertical, retaining clips located on bottom of meter
IP degree of protection IP30 (except connectors)
Maximum number of option
modules
4 (based on maximum operating temperature)
9810 series meter
Mechanical compliance
Vibration
IEC 60068-2-6
IEC 60068-2-57
Shock
IEC 60068-2-27
IEC 60068-2-31, Test Ec Free fall procedure 1
Electrical characteristics
Active energy (Wh) IEC 62053-22 Class 0.1 S
Reactive energy (VARh) IEC 62053-24 Class 0.5 S
Power monitoring device (PMD) IEC 61557-12 PMD/SD/K70/0.2 and PMD/SS/K70/0.2
Active power (P) IEC 61557-12 Class 0.1
Reactive power (Q
V
) IEC 61557-12 Class 1
Apparent power (S
V
) IEC 61557-12 Class 0.2
Apparent energy (E
apV
) IEC 61557-12 Class 0.2
Current (I) IEC 61557-12 Class 0.1
Voltage (U) IEC 61557-12 Class 0.1
Frequency (f) IEC 61557-12 Class 0.02
Measurement accuracy