Meter security configuration
Meter security configuration using ION Setup consists of the following tasks:
1. Open a Security Configuration File
2. Configure the meter security settings
3. Push the updated security settings to the meter
4. Store the updated SCF file
Opening a meter security configuration file
Meter security settings are stored in an encrypted Security Configuration File (SCF).
Use ION Setup to open a SCF file.
Prerequisites:
•
Meter connection using ION Setup.
•
Login credentials.
•
Security configuration access privileges.
To open the meter security configuration file:
1. In ION Setup, select the meter, and then open Setup Assistant.
2. Click Security > Security Mode > Edit.
3. Enter the meter password, and then click OK.
4. Select the SCF file that you want to edit, and then click Open.
NOTE: We recommend that you use Advanced security mode.
For more information on SCF files, see "Storing Security Configuration Files" on page 42.
The meter security configuration settings open in the ION Setup Security wizard.
Next, configure the meter security settings.
Configuring the meter security settings
After you open a SCF file, IONSetup displays the security settings in a Security wizard.
Use the ION Setup Security wizard to complete the following security configuration tasks:
•
"Changing the default password" on page 34
•
"Disabling and enabling meter configuration options" on page 34
•
"Disabling and enabling webpages and time sync sources" on page 35
•
"Defining lockout and event timeout" on page 36
•
"Editing meter access event logging" on page 37
•
"Limiting user access" on page 39
•
"Creating and changing user passwords" on page 40