Communications 9810 series - User manual
109 7EN05-0390-08
8. In the Modbus Slave Map Setup screen you can click Delete to remove a Modbus register,
Set Name to create a new name for the set of additional data mapped to Modbus, or Save
As to save the additional data you have mapped to Modbus as a separate file.
9. Click Finish to complete your meter’s Modbus client configuration and return to the Setup
Assistant.
Ethernet gateway
Ethernet gateway is a communications method that allows you to communicate through a
gateway device to a serial network.
When a meter with gateway capabilities is installed on an Ethernet network, a client device (such
as an energy management system) can communicate through the gateway meter to a serial
network of devices connected to the gateway meter’s serial port(s). The maximum number of
devices on the serial network is determined by the limitations of the gateway meter’s serial port.
A LAN/WAN
B Ethernet gateway meter
C Serial RS-485 network of devices
D Terminating resistor
There are two types of Ethernet gateways that you can configure on your meter:
EtherGate A single TCP connection communicates through the gateway meter to a serial
network of devices.
Modbus gateway Up to a maximum of 32 Modbus client TCP connections communicate
through the gateway meter to a serial network of Modbus devices.