Parameter Values Description
I5 Sec 1–999,999
I5 current transformer's secondary winding
current rating
Scale Rev
Param
ON, OFF
Specifies whether revenue readings are
presented as primary or secondary side values
(ON = primary side, OFF = secondary side)
1
Demo mode is for demonstration only, and does not use the meter input terminals to display
values.
Using the Phasor Viewer
Phasor diagrams can help verify or troubleshoot issues with voltage and current input wiring.
Use ION Setup’s Phasor Viewer to display a real-time phasor diagram of the voltage and current
input signals.
To use the Phasor Viewer:
1. Start ION Setup and open the Setup Assistant for your meter.
2. Click Metering Setup > Phasor.
3. Select Phasor Viewer and click Show.
4. To change the polarity of the voltage or current inputs, click Show Setup to display the
Polarity Settings.
Select the box beside the input you want to invert polarity, then click Apply to Meter.
Basic setup using the webpages or display
You can use the meter webpages or display to configure basic metering parameters.
Using the webpages: Navigate to Setup > Metering.
Using the display: Navigate to Setup Menu > Meter Setup.