To apply security settings to multiple meters:
1. Open ION Setup > select the meter > Setup Assistant.
2. Security > Security Mode > Send. The Open Security Configuration file dialog box opens.
3. Open the meter security configuration file.
TIP: Open the security log file to determine the SCF file you want. See "Opening a meter
security configuration file" on page 33 for more information.
4. Click Yes to confirm the security update.
The security settings in the SCF file are sent to the meter.
5. Click Exit.
Updating passwords on multiple meters
Use the ION Setup Diagnostics tool to update passwords on multiple meters at the same time.
Prerequisites:
•
Meter connection using ION Setup.
•
Login credentials.
•
Security configuration access privileges.
NOTICE
DATA LOSS
Failure to follow these instructions can result in loss of data.
Record your device's user and password information in a secure location.
To update passwords on multiple meters:
1. Open ION Setup > select the System.
2. Tools > Diagnostics. The Systems diagnostics: System dialog box opens.
3. Select the Tools tab > Advanced Security Password Updater.
4. Click Open.
5. Select the meters that need a password update.
6. Click Set Info.
7. Click Start.
8. Click Allow passwords to be visible.
9. Select each user, click Password, and then enter a new password.
If the meter is connected to a display, update the password for the Front Panel.
10. Click Start. A Notice message box opens.
9810 series - User manual Cybersecurity
7EN05-0390-08 46