Resets 9810 series - User manual
259 7EN05-0390-08
Reset Description
Master Reset
Clears all cumulative and derived quantities from the meter,
including: demand, peak demand, energy, revenue, and test
mode parameters.
Clears meter event and waveform logs.
Clears COMTRADE waveform records stored in the meter’s
internal SFTP site.
Clears meter data logs.
Peak Demand Reset
Clears meter peak demand values.
NOTE: The peak demand reset has a lockout period that sets the
minimum time allowed between consecutive resets.
Min/Max Reset Clears maximum and minimum values stored in the meter.
Digital Input Count Reset Clears the digital input status change counters.
Harmonics Min/Max Reset
Clears maximum and minimum harmonics values stored in the
meter.
Disturbance Count Reset
Clears the sag/swell event counter. The sag/swell event counter
counts the number of sag/swells that have occurred since the last
reset or meter power-up.
EN50160 Reset
Clears all EN 50160 parameters and statistics accumulated in the
meter.
Option Modules Reset
Resets communications to expansion modules connected to the
meter.
Conditional (Cnd) Energy
Reset
Clears the conditional energy values stored in the meter.
Input Metering Reset Clears the input metering values stored in the meter.
Performing resets using ION Setup
You can reset the meter using ION Setup.
Revenue-locked meters must be unlocked to perform resets that impact revenue data.
Meter resets clear the meter’s onboard data logs and other related information.
NOTICE
DATALOSS
Failure to follow these instructions can result in data loss.
Ensure all important data from the device is saved before performing a reset.