Meter overview
9810 series overview
The 9810 series advanced energy and power quality meter helps meet the needs of your energy
management, power management, and cost management applications.
All Siemens 9810 series meters comply with international metering accuracy standards. You can
customize your meter by loading specialized frameworks, adding optional modules and
incorporating mounting accessories into the physical installation to meet a variety of installation
and application needs.
Measurement accuracy
Third-party international standards-certified:
Class 0,1S for energy
Power Quality Instrument Class A (PQI-A) for all normative IEC 61000-4-30 power quality
metrics
IEC 62053-22, -23, -24 and ANSI C12.20
Power quality
Third-party international standards-certified:
IEC 62586-1, IEC 62586-2, and IEC 61000-4-30
EN 50160, including flicker monitoring
IEEE 519
Root cause analysis and sequence-of-events support
Disturbance Direction Detection
High-speed RMS data capture with pre and post event records
Extended waveform capture
Time quality flag for GPS or PTP time sources
Time synchronization to 1 ms accuracy
Cybersecurity
Meter security with multiple users and access levels
Total control for each communications port and protocol, including protocol lockout
Secure webpages (HTTPS)
Support for meter event logging to a remote server (syslog)
Account management
If your meter’s user access information is lost, you must return the meter to the factory, where
your meter is reset to its factory defaults and all logged data is lost.