WARNING
UNINTENDED OPERATION
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Do not use this device for critical control or protection of persons, animals, property, or
equipment.
To configure digital outputs for IEC 61850 control:
1. Open ION Setup.
2. Ctrl + click on the meter to select it. This switches ION Setup to Advanced mode.
3. IEC 61850 GGIO Onb Modules folder > double-click module > Setup Registers.
4. Select the desired SPCS Control Mode register > Edit. A dialog opens.
5. Select IEC 61850 CtlVAL from the drop-down list box > OK > Inputs.
6. Select the digital output Status register > Delete.
Note: This digital input register must be deleted to prevent a circular reference that will
cause the affected modules to go offline.
7. Click Send.
8. Navigate to the Digital Out Modules folder > double-click on the module selected to control
via IEC 61850.
9. Select the Setup Registers tab and confirm that the Digital Output module’s setup registers
are configured.
10. Inputs > Source register > Edit.
11. Navigate to the IEC 61850 GGIO Onb folder and select the SPCS.stVal output register that
corresponds to the digital output.
12. Click OK > Send.
See ION Reference, available from www.usa.siemens.com/pds, for information about IEC
61850 GGIO and Digital output modules.
Deleting an IEC 61850 configuration file
1. Open SFTP client software. See "Secure File Transfer Protocol (SFTP)" on page 116 for
information about connecting with SFTP client software.
2. Connect to the meter using the meter’s IP address and SFTP port number. See "Protocols,
ports, and connections" on page 72 for information on port numbers.
3. Open the IEC61850 folder in SFTP file directory and delete the CID file.
4. Close SFTP client software.
9810 series - User manual Communications
7EN05-0390-08 126