EMC (electromagnetic compatibility)
EMC standards IEC 62052-11, IEC 61326-1, IEC 61000-6-5
Immunity to electrostatic
discharge
IEC 61000-4-2
Immunity to radiated fields IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to surges IEC 61000-4-5
Immunity to conducted
disturbances
IEC 61000-4-6, IEC 61000-4-16
Immunity to power frequency
magnetic fields
IEC 61000-4-8
Immunity to conducted
disturbances, 2 - 150 kHz
CLC/TR 50579
Immunity to voltage dips and
interruptions
IEC 61000-4-11
Immunity to ring waves IEC 61000-4-12
Conducted and radiated
emissions
EN 55011 and EN 55032 Class B, FCC part 15 Class B,
ICES-003 Class B
Surge withstand capability
(SWC)
IEEE/ANSI C37.90.1
Safety
Safety construction
IEC/EN 61010-1, CAT III, 400 VLN / 690 VLL
UL 61010-1 and CSA-C22.2 No. 61010-1, CATIII, 347 V LN /
600 VLL
IEC/EN 62052-31, Protective Class II
Ethernet communications
Number of ports 2 (switched mode)
Maximum cable length 100 m (328 ft), per TIA/EIA 568-5-A
Cable type CAT5 (or higher)
Connector type Unshielded RJ45 modular connector (2)
Mode 10Base-T, 100Base-TX, Auto-MDIX
Data rate up to 100 Mbps
9810 series - User manual 9810 specifications
7EN05-0390-08 296