Installation and commissioning 9810 series - User manual
68 7EN05-0390-08
1. Start ION Setup and open the Setup Assistant for your meter.
2. Configure the parameters in Metering Setup > Basic.
Parameter Values Description
Volts Mode
4W-WYE, DELTA, 3W-
WYE, SINGLE, DEMO
1
Power system type
PT Prim 1–999,999
Potential transformer's primary winding voltage
rating
PT Sec 1–999,999
Potential transformer's secondary winding
voltage rating
CT Primary 1–999,999
Current transformer's primary winding current
rating
CT
Secondary
1–999,999
Current transformer's secondary winding
current rating
Nominal
Voltage
1–999,999
Nominal voltage (V) used for metering functions
such as harmonic calculations and sag/swell
detection
Nominal
Current
1–999,999
Nominal current (A) used for metering functions
such as harmonic calculations and sag/swell
detection
Nominal
Frequency
50, 60
Nominal frequency (Hz) used for metering
functions such as alarms
Basic tab
3. Configure the parameters in Metering Setup > Advanced, if appropriate.
Parameter Values Description
PhaseOrder ABC, ACB
Power system’s rotation order of voltage
phases
V4 PT Prim 1–999,999
V4 potential transformer's primary winding
voltage rating
V4 PT Sec 1–999,999
V4 potential transformer's secondary winding
voltage rating
I4 Prim 1–999,999
I4 current transformer's primary winding
current rating
I4 Sec 1–999,999
I4 current transformer's secondary winding
current rating
I5 Prim 1–999,999
I5 current transformer's primary winding
current rating
Advanced tab