Parameter Value/Range Description
Dropout Numeric value
Use this setting to provide a value for when the
alarm turns off.
Dropout Delay Numeric value
This specifies the number of seconds the input
must be below the alarm dropoff value before the
alarm turns off.
Alarm Priority
None, Info Only, Low,
Medium or High
Specifies the priority level of the standard alarm.
When priority is set to Info Only, the alarm does
not appear on the display.
Custom Priority 0–255
Select custom priority to view and configure the
event priority of the event associated with the
alarm. The event log cutoff value is displayed for
reference; priorities above the cutoff are stored in
the meter’s event log.
Sag/swell overview
Your meter monitors your power system’s voltage and current for sags and swells (INCITS
(CBEMA) Type 2 and Type 3 disturbances).
When sag/swell limits are defined and alarming is enabled, the meter reports the disturbance’s
magnitude and duration, and logs data and waveform records associated with the disturbance.
You can manually enter the limits (criteria) used by the meter to identify a sag or swell, or you can
have your meter learn sag/swell limits by monitoring your power system.
Configuring sag/swell alarms using ION Setup
To configure sag/swell alarm settings using ION Setup:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Alarming > Sag/Swell.
4. Select the parameter you want to configure and click Edit.
The setup dialog box for that parameter appears.
5. Configure the parameters as required.
The values you need to set vary depending on the type of sag/swell alarm you are
configuring.
Parameter Value/Range Description
Enable/Disable
Enabled or
Disabled
Specifies if sag/swell recording and alarming is enabled.
Voltage sag/swell setup parameters
9810 series - User manual Alarms and alerts
7EN05-0390-08 186