Communications 9810 series - User manual
111 7EN05-0390-08
6. Change the settings, and then click OK to save the changes.
Parameter Setting
Protocol EtherGate or Secure EtherGate
Baud Rate
Serial Port
Serial port settings must match the settings for all connected
serial devices.
7. Create an Ethernet gateway site to access the serial network of devices through your
gateway meter.
Configuring EtherGate or Secure EtherGate using the webpages
To configure EtherGate or Secure EtherGate communications using the meter webpages:
1. Connect to your meter’s webpages.
2. Navigate to Setup > Serial Port.
3. Expand Basic Settings or Advanced Settings and modify the settings for the serial port you
are configuring for EtherGate communications (COM1 / RS485#1 or COM4 / RS485#2).
4. Change the settings, then click Apply. Click Yes to save the changes.
Parameter Setting
Protocol EtherGate or Secure EtherGate
Baud Rate
Serial Port
Serial port settings must match the settings for all connected
serial devices
You can use ION Setup to create an Ethernet gateway site and access the serial network of
devices connected through the EtherGate meter.
Configuring EtherGate or Secure EtherGate using the display
To configure EtherGate or Secure EtherGate communications using the meter display:
1. Press the Home button.
2. Navigate to Setup Menu > Communications Setup.
3. Press the Select button.
4. Scroll then select COM1 Setup or COM4 Setup.
5. Highlight the parameter and press Edit. Enter the meter password if prompted, change the
setting, then press Select to save the changes.
Parameter Setting
Protocol EtherGate or Secure EtherGate
Baud Rate
Serial Port
Serial port settings must match the settings for all connected
serial devices