Configuring transient alarms using ION Setup
To configure transient alarm settings using ION Setup:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Alarming > Transient.
4. Select Transient/Waveshape and click Edit.
The setup dialog box for that parameter appears.
5. Configure the parameters as required.
Parameter Value/Range Description
Enabled/Disabled
Enabled or
Disabled
Specifies if transient recording and alarming is
enabled.
Nominal 1–999,999
Specifies the nominal voltage value used for transient
detection.
Threshold
Percentage of
nominal
Specifies the threshold expressed as a percentage of
the nominal voltage, plus 100.
For example, if you want transients recorded when
voltage deviates from nominal by 20%, enter 120.
Alarm priority See description
Select the alarm priority you want to associate with
Transient alarms.
To stop an alarm from being displayed without
affecting other meter features, set the alarm priority to
Info Only.
Transient setup parameters
Configuring digital input alarms using ION Setup
To configure digital alarm settings using ION Setup:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Alarming > Digital Input.
4. Configure the digital input alarm settings by selecting an input and clicking Edit. Some
settings are not configurable and are grayed out.
5. Click Save to save the changes to the meter.
9810 series - User manual Alarms and alerts
7EN05-0390-08 188