Power quality 9810 series - User manual
217 7EN05-0390-08
The waveform log set for the extended waveform capture = [pre-trigger records] + [actual trigger
record] + [post-trigger records]. The total waveform records captured in this example is 2 + 1 + 6 =
9.
When extended waveform capture is enabled, both Buffer Depth and Depth setup registers must
be set to a positive integer multiple of the waveform log set.
NOTE: The COMTRADE module does not support extended waveform capture. The
COMTRADE files saved are only for the trigger waveform record.