Parameter Values Description
Baud Rate
2400, 4800, 9600, 19200,
38400, 57600, 115200
Sets the data rate, in bits per second
Rx Timeout
1
0.1–15
Sets the transmit delay (timeout for receiving
an entire message from a device) in seconds.
Unit ID 1–9999
Sets the meter’s unique ID on the RS-485
network
Note: Modbus serial device range 1 to 247
Serial Port
8N1, 8N2, 8E1, 8E2, 8O1,
8O2
Sets the parity and stop bits for the port
RS485 Bias OFF, ON
Turns on biasing on the client device over the
RS-485 port
1
Only applies to a subset of protocols.
Configuring serial communications settings using the webpages
You can use the meter’s webpages to configure your serial communications settings.
Before configuring serial parameters, make sure you have a unique unit ID for your meter and
know the serial network settings (protocol, baud rate, parity and stop bits).
To configure the meter’s serial communications settings using the meter webpages:
1. Connect to your meter’s webpages using the meter’s IPv4 address or its IPv6 link local
address, or use self-discovery then double-clicking the meter’s network icon.
2. Navigate to Setup > Serial Port.
3. Enter the appropriate value for the settings.
4. Click Advanced Settings to configure additional settings, if needed (for example, RS485
biasing or Rx Timeout).
Parameter Values Description
Protocol
ION, Modbus RTU,
Modbus Master, DNP
v3.00, DLMS, EtherGate,
GPS: Truetime/Datum,
GPS: Arbiter, GPS:
Arbiter-Vorne, Factory,
None
Sets the communications protocol for your
meter’s RS-485 port
The NONE setting stops communications
using this port.
Baud Rate
2400, 4800, 9600, 19200,
38400, 57600, 115200
Sets the data rate, in bits per second
Unit ID 1–9999
Sets the meter’s unique ID on the RS-485
network
NOTE: Modbus serial device range 1 to 247
Basic serial communications settings available using the webpages
9810 series - User manual Communications
7EN05-0390-08 90