13.12.2 Other applicable documents
Pay attention to the following additional documents and information:
164).
-
ler“ on page 189).
K08 K17 (see “14.4.4 Data sheet for relay K08
13.12.3 Selecting the installation location
local conditions.
For the purpose of example, this section describes water warning system installation for an Upflow unit.
Installation instructions for Upflow and Downflow units:
humidifier.
-
sary, install a pressure relief valve in the feed water pipe.
– Stop cock.
– Pressure resistance: ≥ 8 bar.
– Temperature resistance: ≥ +40 °C.
– Flowrate: min. 0.6 l/min.
– Diameter 1/2".
Installation instructions for Upflow units:
(B16) in the EC Tower at the lowest point of the floor panel.
– Install the 2nd sensor (B17) in the EC Tower installation location at the lowest point of the room.
Installation instructions for Downflow units without blow-out plinth:
(B16) in the intermediate floor at the lowest point.
Installation instructions for Downflow units with blow-out plinth:
(B16) in the blow-out plinth on the floor panel.
– Install the 2nd sensor (B17) in the EC Tower installation location at the lowest point of the room.