EasyManua.ls Logo

Stulz EC Tower ECD 91 - 6.3 Setting the outdoor unit model on DIP switch S1

Stulz EC Tower ECD 91
206 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
154 EN/01.2019/G22  © STULZ GmbH – all rights reserved
ec tower technical manual
6.2.2 Setting the functions for Program 8 on DIP switch S2
The following table lists the functions for Program 8 in brief. See „4. InterfaceIIIk functions“ for a detailed
description of the functions.
DIP switch Status Function
S21
ON
OFF
Interface
IIIk is master
Interface
IIIk is slave
S22
ON
OFF
X4b-K2, operating signal; X4c-K3, heating signal
X4b-K2, compressor signal; X4c-K3, defrost signal
S23 | S24 No function, switch setting is always OFF
S25
ON
OFF
Forced mode
No function
S26
ON
OFF
All digital outputs are closed without a signal (NC)
All digital outputs are open without a signal (NO)
S27
ON
OFF
Setting determines the value that is shown on the 7-segment display (see “3.5 7-segment
display“ on page 149).
S28
ON
OFF
Setting determines the value that is shown on the 7-segment display (see “3.5 7-segment
display“ on page 149).
6.3 Setting the outdoor unit model on DIP switch S1
6.3.1 For FDC outdoor units: Setting DIP switch S1 on the Interface III k
Procedure for FDC outdoor units
1. On the outdoor unit board of the FDC outdoor unit, set DIP switch SW43 to ON (see other applicable
documents: FDC series Technical Manual).
2. Define which FDC outdoor unit is installed on site (see “Table 1: Setting the outdoor unit model with DIP
switches S15 to S18“ on page 155).
3. Set DIP switches S15 to S18 in line with the FDC outdoor unit installed on site (see “Table 1: Setting the
outdoor unit model with DIP switches S15 to S18“ on page 155).
6.3.2 For SRC outdoor units: Setting DIP switch S1 on the Interface III k
NOTE

Procedure for SRC outdoor units
1. Replace the Thi-A sensor with a 5k fixed resistor (see other applicable documents: Technical Manual for
heat exchanger connection module).
2. Set the temperature setpoint on the wired remote control:
18°C.
30 °C.
3. Lock the wired remote control to prevent the temperature setpoint from being changed.
Alternatively: Disable the wired remote control via a signal to digital input X2b-D3. The InterfaceIIIk is
set to Center.

Table of Contents

Related product manuals