155 © STULZ GmbH – all rights reserved EN/01.2019/G22
ec tower technical manual
4. Define which SRC outdoor unit is installed on site (see “Table 1: Setting the outdoor unit model with DIP
switches S15 to S18“ on page 155).
5. Set DIP switches S15 to S18 in line with the SRC outdoor unit installed on site (see “Table 1: Setting the
outdoor unit model with DIP switches S15 to S18“ on page 155).
The table below shows the settings for the outdoor unit model using DIP switches S15 to S18:
Outdoor unit model DIP switch
FDC outdoor unit Enabled SRC outdoor unit Enabled S15 S16 S17 S18
- - SRC 40 ZSXS
OFF OFF ON OFF
- - SRC 50 ZSXS
FDC 71 VNX
- - ON OFF ON OFF
FDC 140 VS
- -
ON ON ON OFF
FDC 140 VSX
- -
- - SRC 50 ZSS
OFF OFF OFF ON
FDC 140 VSA
- - OFF OFF ON ON
- - SRC 60 ZSXS
OFF ON ON ON
FDC 200 VSA
- -
ON ON ON ON
FDC 250 VSA
- -
Table 1: Setting the outdoor unit model with DIP switches S1-5 to S1-8
6.4 Analog input
NOTE
SW43 to ON on the outdoor unit board of the
FDC outdoor unit (see FDS series Technical Manual).
delivered. The input must remain permanently enabled.
X3S is only evaluated if a signal is present at digital input X2b-D4 (see “4.1
Analog input functions“ on page 149).
becoming distorted by electrical induction.