8. Troubleshooting
The following tables lists faults the InterfaceIIIk may experience. If the problem cannot be rectified, please
contact Technical Support.
Problem Possible cause and remedy
Changes to DIP switch settings are not
applied
InterfaceIIIk was still under voltage when the DIP switches were changed.
Remedy:
- Before changing the DIP switch settings, cut the power to the InterfaceIIIk by
pulling out the connector X1 from the InterfaceIIIk.
- Change the settings of the DIP switches.
- Re-insert connector X1.
InterfaceIIIk does not initialize in the
remote control bus
or
Indoor air conditioning unit not responding
to InterfaceIIIk commands
The InterfaceIIIk and wired remote control are both configured as master.
Remedy:
- Check the roles assigned in the X/Y remote control bus, see “4.3.3 Status of the
InterfaceIIIk (master/slave)“ on page 151.
- Configure the wired remote control as master and the InterfaceIIIk as slave.
- Check the DIP switch setting 21 on the InterfaceIIIk and correct if necessary.
Error message E1 (communication error) on
the InterfaceIIIk
or
Error message E1 (communication error) on
the wired remote control
The InterfaceIIIk and wired remote control are both configured as slave.
Remedy:
- Check the roles assigned in the X/Y remote control bus, see “4.3.3 Status of the
InterfaceIIIk (master/slave)“ on page 151.
- Configure the wired remote control as master and the InterfaceIIIk as slave.
- Check the DIP switch setting 21 on the InterfaceIIIk and correct if necessary.
Error message E1 (communication error) on
the wired remote control
InterfaceIIIk faulty.
Remedy:
- Switch off the entire system and secure so it cannot be switched back on.
- Unplug all connectors of the InterfaceIIIk, replace the InterfaceIIIk
and re-insert all connectors.
- Check the configuration of the InterfaceIIIk.
- Switch the system back on; reset errors on the wired remote control if necessary.
Air conditioning unit is cooling although
Heating mode has been selected
The outdoor air conditioning unit is in defrosting mode.
Remedy:
10 minutes).
Programs 8 has recurrent problems with
high or low pressure
DIP switch setting on outdoor air conditioning unit incorrect.
Remedy:
- On series FDC71 to FDC250 outdoor air conditioning units, set DIP switch
SW43 on the outdoor air conditioning units to ON .
In Program 8, the analog input receives a
voltage > 1VDC, but transferred frequency
request remains at 0Hz
Open circuit at analog input
X3S.
Remedy:
- Check cable and connection of analog inputX3S for open circuits.
- Replace cable if necessary.