Steam humidifier
components
Maintenance interval
After the first
operating hour
Every fortnight
or after 300 ope-
rating hours
Every quarter or
after 1,000 ope-
rating hours
Yearly or after
2,500 operating
hours
Every 5 years
or after 10,000
operating hours
On steam cylinder,
between electrodes
during operation.
X
On steam cylinder,
components.
X X
condensate and water
hoses for damage.
X
Flush water drain of
steam humidifier.
X
deposits, deformation
X
Replace steam cylinder.
X
6.2 Replacing the steam cylinder
NOTE
used!
-
ual of your EC Tower, see “2.4 Other applicable documents“ on page 9).
The steam cylinder needs to be replaced if increasing calcification has caused the electrodes to become iso-