97 © STULZ GmbH – all rights reserved EN/01.2019/G22
ec tower technical manual

Flexible canvas fitting
Procedure
1. Switch off the air conditioning unit.
2. Fit suitable sealing tape on the contact surfaces
(1) on both sides of the flexible canvas fitting.
3. Install the adapter panel (see “13.6Installing the
adapter panel for Upflow units“ on page 94).
4. Fasten the flexible canvas fitting to the adapter
panel .
5. Connect the flexible canvas fitting to the air duct.
Installation
1
EC Tower
51-5670-16 ECTower_Vorlage.indd 1
03.08.16 16:31