121
I/O Check The I/O check flowchart is based on the following ladder diagram section.
10500
00002
(LS1)
00003
(LS2)
SOL1 malfunction.
SOL1
10500
Yes
Monitor the ON/OFF
status of IR 10500
with a Peripheral
Device.
No
Is the IR 10500 out-
put indicator operat-
ing normally?
Check the voltage at the
IR 10500 terminals.
Wire correctly. Replace terminal
connector.
Operation
O.K.?
Start
Is output wiring
correct?
Is terminal
block making proper
contact?
Disconnect the external wires
and check the conductivity of
each wire.
No
Yes
Check output device
SOL1.
Operation
O.K.?
Replace the Output
Unit.
Yes
No
No
Yes
No
Operation
O.K.?
NoYes
Yes
A
To
next
page
Troubleshooting Flowcharts
Section 4-6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sysmac CQM1 and is the answer not in the manual?

Sysmac CQM1 Specifications

General IconGeneral
ManufacturerOmron
Operating Temperature0 to 55°C
Humidity10 to 90% RH (non-condensing)
Power Supply100 to 240 VAC or 24 VDC (depending on model)
Programming LanguageLadder Diagram, Instruction List
Communication PortsRS-232C
ExpansionExpansion I/O units available
Analog I/OAvailable via expansion units
Instruction SetBasic and advanced instructions
Vibration Resistance10 to 57 Hz, 0.075 mm amplitude