E6582062
5-55 5. [Fundamental operation] How to use parameters
3
4
5
9
2) Setting contents of PID control
Set <F359: PID control 1> to "1: Process PID control".
Set <ACC: Acceleration time 1> and <dEC: Deceleration time 1> to the time that is suitable for
the system. Refer to [5. 2. 4].
To limit the setting values, set the following parameters.
To limit the set value: <F367: PID1 set value upper-limit>, <F368: PID1 set value lower-limit >
To limit the output frequency: <UL: Upper limit frequency>, <LL: Lower limit frequency>
(Refer to [5. 2. 3].)
Title Parameter name Adjustment range
Default
setting
F389 PID1 set value select 0: selected by FMOd/F207
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5: Terminal AI5 (option)
6 - 11: -
12: FPId
13, 14: -
15: Terminal Up/Down frequency
16: Pulse train
17: High resolution pulse train (option)
18, 19: -
20: Embedded Ethernet
21: RS485 communication (connector 1)
22: RS485 communication (connector 2)
23: Communication option
0
F360 PID1 feedback input
select
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5: Terminal AI5 (option)
6 - 16: -
17: High resolution pulse train (option)
0
Title Parameter name Adjustment range Unit
Default
setting
F359 PID control 1 0: Disabled
1: Process PID control
2: Speed PID control
3: Easy positioning P control
4: Dancer control
5 - 10: -
11: Minus Process PID control
12: Minus Speed PID control
13: Minus Easy positioning P control
14: Minus Dancer control
0
F367 PID1 set value upper-
limit
0.0 - FH Hz 50.0/60.0
F368 PID1 set value lower-limit 0.0 - F367 Hz 0.0

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m