E6582062
6. [Advanced] How to use parameters 6-102
4
4
6
9
2) In case of torque limit
If, during power running, the output torque reaches the value for <F441: Power running torque
limit level 1> or more, and continues for the period of time set for <F452: Stall detection time
during power running>, the trip "Ot2" will occur. In case F452=0, this function is not activated
(Ot2 trip does not occur).
Reference
How to operate the operation panel -> Refer to [3. 1. 1].
How to switch display mode on the operation panel -> Refer to [3. 1. 2].
Procedure to change parameter setting -> Refer to [4. 2. 3]
“0t2” Trip
Output frequency (Hz)
Output torque (%)
Below
<F452>
Time (s)
Time (s)
<F441>
<F452>