E6582062
6. [Advanced] How to use parameters 6-146
4
4
6
9
6. 30. 18 Rush current suspension relay control
<F635: Rush current suppression relay delay time>
Function
This function is used for DC input or when multiple inverters are connected with DC section and
when the rush current suspension resistor relay needs to be controlled.
Parameter setting
Guideline for the setting
When the voltage of DC section in the inverter has reached the specified voltage, after a lapse of
setting time by <F635: Rush current suppression relay delay time> +500ms (basic wait time), the
rush current suspension relay is turned on.
Title Parameter name Adjustment range Unit Default setting
F635 Rush current
suppression relay delay
time
0.0 - 2.5 s 0.0
Reference
How to operate the operation panel -> Refer to [3. 1. 1].
How to switch display mode on the operation panel -> Refer to [3. 1. 2].
Procedure to change parameter setting -> Refer to [4. 2. 3]
0.0HzSTOP
14:03
F635 : Rush current relay time
Min: 0.0 Max: 2.5
X1000 X100 X10 X1
S
0.0
Voltage in the DC section
Rush current suppression relay
ON
<F635>
+500ms