METASYS N2 OBJECTS
FMS-1650
- 71 -
TRIATEK reserves the right to change product specifications without notice.
TRIATEK reserves the right to change product specifications without notice.
Object Instance Functional Description Read or Write
ADF - 24 AI-2 Low Alarm Setpoint Read/Write
ADF - 25 AI-2 Low Warning Setpoint Read/Write
ADF - 26 AI-2 High Warning Setpoint Read/Write
ADF - 27 AI-2 High Alarm Setpoint Read/Write
ADF - 28 AI-3 Low Alarm Setpoint Read/Write
ADF - 29 AI-3 Low Warning Setpoint Read/Write
ADF - 30 AI-3 High Warning Setpoint Read/Write
ADF - 31 AI-3 High Alarm Setpoint Read/Write
ADF - 32 AI-4 Low Alarm Setpoint Read/Write
ADF - 33 AI-4 Low Warning Setpoint Read/Write
ADF - 34 AI-4 High Warning Setpoint Read/Write
ADF - 35 AI-4 High Alarm Setpoint Read/Write
ADF - 36 TI-1 Low Alarm Setpoint Read/Write
ADF - 37 TI-1 Low Warning Setpoint Read/Write
ADF - 38 TI-1 High Warning Setpoint Read/Write
ADF - 39 TI-1 High Alarm Setpoint Read/Write
ADF - 40 TI-2 Low Alarm Setpoint Read/Write
ADF - 41 TI-2 Low Warning Setpoint Read/Write
ADF - 42 TI-2 High Warning Setpoint Read/Write
ADF - 43 TI-2 High Alarm Setpoint Read/Write
ADF - 44 Humidity Network Variable (writable) Read/Write
ADF - 45 Temperature Network Variable (writable) Read/Write
ADF - 46 Air Changes Network Variable (writable) Read/Write
ADF - 47 Differential Pressure Network Variable (writable) Read/Write
ADF - 48 Air Flow based on Flow Input at AI-1 Read-Only
ADF - 49 Air Flow based on Flow Input at AI-2 Read-Only
ADF - 50 Air Flow based on Flow Input at AI-3 (default: Supply Flow) Read-Only
ADF - 51 Air Flow based on Flow Input at AI-4 (default: Exhaust Flow) Read-Only
ADF - 52 Volumetric Offset (Supply Flow – Exhaust Flow) Read-Only
ADF - 53 Volumetric Offset Setpoint Read-Write
ADF - 54 AO-1 Override Level Read-Write
ADF - 55 AO-2 Override Level Read-Write
ADF - 56 AO-3 Override Level Read-Write
ADF - 57 AO-4 Override Level Read-Write
Internal Integer Values
ADI - 1 AI-1 Isolation Mode: 1=positive, 2=negative, 3=neutral Read/Write
ADI - 2 AI-1 Alarm Status: 1=normal, 2=warning, 3=alarm Read-Only
ADI - 7 AI-2 Isolation Mode: 1=positive, 2=negative, 3=neutral Read/Write
ADI - 8 AI-2 Alarm Status: 1=normal, 2=warning, 3=alarm Read-Only
ADI - 9 AI-3 Alarm Status: 1=normal, 2=warning, 3=alarm Read-Only
ADI - 10 AI-4 Alarm Status: 1=normal, 2=warning, 3=alarm Read-Only
ADI - 11 TI-1 Alarm Status: 1=normal, 2=warning, 3=alarm Read-Only
ADI - 12 TI-2 Alarm Status: 1=normal, 2=warning, 3=alarm Read-Only
Metasys
®
N2 Objects