Typically, moisture in transformer oil measurement with HMP378F has a ppm accuracy of
±10 % of the reading. If additional accuracy is needed, see HMP378F calculation model with oil-
specific coecients (page 118).
9.4.2 HMP378F calculation model with oil-specific coecients
For additional accuracy, an oil-specific calculation model can be used in HMP378F for mineral
transformer oils. A specific model is always needed for other transformer oil/fluid types. Note
that the calculation is only supported for stable dielectric fluids.
For oil-specific coecients, an oil sample has to be sent to Vaisala for modeling. As a result,
the specific coecients (A and B: see formula in HMP378F calculation model with average oil
coecients (page 117)) for the oil are determined by Vaisala. Using these coecients increases
measurement accuracy.
You can configure the determined coecients of the oil into use with Insight PC software, or
contact Vaisala about setting the coecients. For configuration instructions, see Configuring
calculation coecients (page 117).