Table 9 Allowed ambient temperature ranges
Equipment part Allowed ambient temperature range
Transmitter body -40 °C … +60 °C (-40 … +140 °F)
Probe body -40 °C … +60 °C (-40 … +140 °F)
Probe head HMP371 Temperature class T4:
-40 °C … +60 °C (-40 … +140 °F)
Probe head HMP373 Rubber cable version:
Temperature class T6:
-40 °C … +55 °C (-40 … +131 °F)
Temperature class T5:
-40 °C … +80 °C (-40 … +176 °F)
FEP cable version:
Temperature class T6:
-40 °C … +55 °C (-40 … +131 °F)
Temperature class T5:
-40 °C … +100 °C (-40 … +212 °F)
Temperature class T4:
-40 °C … +120 °C (-40 … +248 °F)
Probe heads HMP374, HMP375, HMP377,
HMP378, HMP378F, and HMP378H
Temperature class T6:
-70 °C … +55 °C (-94 … +131 °F)
Temperature class T5:
-70 °C … +100 °C (-94 … +212 °F)
Temperature class T4:
-70 °C … +135 °C (-94 … +275 °F)
Temperature class T3:
-70 °C … +180 °C (-94 … +356 °F)
3.2.2.1 Specific conditions of use
With the installation of the equipment in Zone 0 Group II area it has
to be ensured that sparks due to impact or friction do not occur.
CAUTION!
Wiring requirements
The cable glands and cables used for wiring the device must not impair the Ex protection.
Unused lead-throughs must be sealed using Ex compliant plugs.
Chapter 3 – HMT370EX regional safety certification information
23