Introduction Alarm Message Quick Reference Index
4
Alarm Message Quick Reference Index
Table 1: Alarm Message Table
Alarm Type Cause Action
Annual Test Fail Tank In-tank annual leak test failed Rerun in-tank leak test. If second test fails,
call for service.
Autodial Fail Comm System failed to connect to a remote
receiver after programmed number of
tries.
Check remote receiver.
Delivery Needed Tank Product level dropped below preset
limit.
Call for delivery.
Gross Test Fail Tank In-tank leak test failed. Rerun in-tank leak test. If second test fails,
call for service.
High Water Tank Water detected in tank exceeds preset
limit.
Remove water from the tank.
Invalid Fuel Height Tank Fuel level dropped to a point below
the minimum detectable level or only
one float is present.
Call for delivery.
Low Product Tank Tank level dropped below preset limit. Call for delivery.
Low Temperature Tank Probe temperature dropped below -
4°F (-20°C). For Low Temperature
probes, below -4F (-4C).
Probe returns to normal operation after
probe temperature rises above 0°F
(-17.7°C). For Low Temperature probes,
above -36°F (-38°C)
Max Product Tank Product level rose above preset limit. Stop delivery.
Overfill Tank Potential overflow of tank may occur. Stop delivery. Check for spillage.
Periodic Test Fail Tank In-tank leak test failed. Rerun in-tank leak test. If second test fails,
call for service.
Probe Out Tank Hardware failure - probe or intercon-
necting wiring to console.
Call for service.