2
GENERAL INFORMATION
Table 2.7: Water Cooled Models - 5 level
Rated Current
(1)
Motor Rated Power
(2)
Dissipated Power
(3)
ND HD
ND HD
ND HD
[A]
Models
[HP] [KW] [HP] [KW]
[KW]
Frame
size
6000 - 6300 V
276 257
MVW01 0276 T 6300
3380 2520 3140 2340 21.83 20.57
326 299
MVW01 0326 T 6300
3990 2970 3660 2720 25.31 23.4
384 347
MVW01 0384 T 6300
4700 3500 4240 3160 29.61 26.83
452 403
MVW01 0452 T 6300
5530 4120 4930 3670 35.03 31.08
480 433
MVW01 0480 T 6300
5870 4370 5300 3950 37.49 33.27
533 468
MVW01 0533 T 6300
6520 4860 5720 4270 42.01 37.46
624 559
MVW01 0624 T 6300
7630 5690 6840 5090
45.77
40.91
C2W
735 645
MVW01 0735 T 6300
8990 6700 7890 5880 47.78 43.00
863 758
MVW01 0863 T 6300
10560 7860 9270 6910 65.95
57.15
912 823
MVW01 0912 T 6300
11160 8310 10070 7500 69.69 62.04
1013 889
MVW01 1013 T 6300
12390 9230 10870 8100 74.20 65.08
1186 1062
MVW01 1186 T 6300
14510 10810 12990 9680 86.87
77.74
C3W
1288 1149
MVW01 1288 T 6300
15760 11740 14060 10470 99.74 87.78
1368 1234
MVW01 1368 T 6300
16730 12470 15100 11250 105.93 94.27
1519 1334
MVW01 1519 T 6300
18580 13840 16320 12160 116.81 102.12
1778 1593
MVW01 1778 T 6300
21750 16200 19490 14520 136.73 121.94
3xC2W
1824 1646
MVW01 1824 T 6300
22310 16620 20140 15000 139.39 124.09
2026 1778
MVW01 2026 T 6300
24780 18460 21750 16200 148.40 130.15
2372
2124
MVW01 2372 T 6300
29020 21620 25980 19360 173.74 155.48
2xC3W
2589
2274
MVW01 2589 T 6300
31670 23590 27820 20720 197.85
171.44
2736 2469
MVW01 2736 T 6300
33470 24930 30200 22500 209.08 186.14
3039 2667
MVW01 3039 T 6300
37180 27700 32620 24310 222.60 195.23
3558 3186
MVW01 3558 T 6300
43520 32430 38970 29040 260.61 233.22
3xC3W
6600 - 6900 V
267 250
MVW01 0267 T 6900
3580 2670 3350 2500 22.09 20.94
313 290
MVW01 0313 T 6900
4190 3120 3890 2890 25.32 23.68
368 337
MVW01 0368 T 6900
4930 3670 4520 3360 29.42 27.08
432 391
MVW01 0432 T 6900
5790 4310 5240 3900 34.54 31.22
460 423
MVW01 0460 T 6900
6160 4590 5670 4220 37.19 33.82
507
455
MVW01 0507 T 6900
6790 5060 6100 4540 42.99 39.47
598 525
MVW01 0598 T 6900
8010 5970 7030 5240 48.30 42.28
C2W
699 627
MVW01 0699 T 6900
9370 6980 8400 6260 55.70 50.12
820 736
MVW01 0820 T 6900
10990 8180 9860 7350 66.08 58.96
874 803
MVW01 0874 T 6900
11710 8720 10760 8010 69.30 63.14
962 865
MVW01 0962 T 6900
12890 9600 11590 8630 82.82 73.52
1140 1000
MVW01 1140 T 6900
15270 11380 13400 9980 90.70 79.50
C3W
1231
1114
MVW01 1231 T 6900
16490 12290 14930 11120 97.21 87.24
1311 1205
MVW01 1311 T 6900
17560 13090 16140 12030 103.53 94.40
1445
1297
MVW01 1445 T 6900
19360 14420 17380 12950 114.60 102.84
1704 1496
MVW01 1704 T 6900
22830 17010 20040 14930 135.14 118.62
3xC2W
1748 1606
MVW01 1748 T 6900
23420 17450 21520 16030 138.59 126.30
1924 1730
MVW01 1924 T 6900
25780 19200 23180 17270 165.61 147.04
2280 1994
MVW01 2280 T 6900
30550 22760 26720 19900 181.40 159.01
2xC3W
2460 2208
MVW01 2460 T 6900
32960 24550 29580 22040 195.04 173.63
2622 2409
MVW01 2622 T 6900
35130 26170 32280 24040 207.88 189.43
2886 2595
MVW01 2886 T 6900
38670 28810 34770 25900 229.62 206.32
3420 3000
MVW01 3420 T 6900
45820 34140 40190 29940
272.11
238.52
3xC3W
(1) Overload capacity:
HD: Heavy Duty: 150 % overload during 60 seconds every 10 minutes.
MX: Maximum Current: overload is not allowed.
(2) The motor rated power takes into account the operation with 0.87 power factor and 96 % efficiency at full load;
(3) Dissipated Power in the power arms and 3x12-pulse rectifier.
✓
NOTE!
The motor rated powers are only orientations, and the correct inverter selection must be done as a function of the rated current
of the motor to be used, as well as the overloads related to the application.
MVW01 | 2-11