256 Parameters
Wake < ref If the process actual value (see group 28 Procact sel)
remains above the process setpoint (see group 29 Setpoint
sel) multiplied by the wake-up level for longer than the wake-
up delay (77.11 Wake up delay), the drive wakes up. See the
diagram below.
1
Wake > ext If the signal selected by parameter 77.09 Wake up ext src
remains below the wake-up level (77.10 Wake up level)
longer than the wake-up delay (77.11 Wake up delay), the
drive wakes up.
2
Wake < ext If the signal selected by parameter 77.09 Wake up ext src
remains above the wake-up level (77.10 Wake up level)
longer than the wake-up delay (77.11 Wake up delay), the
drive wakes up.
3
77.09 Wake up ext src Selects the signal source for parameter 77.09 Wake up ext
src, selections Wake > ext and Wake < ext.
AI1 02.04 AI1 (see page 113). 1073742340
AI1 scaled 02.05 AI1 scaled (see page 113 ). 1073742341
AI2 02.06 AI2 (see page 113). 1073742342
AI2 scaled 02.07 AI2 scaled (see page 113 ). 1073742343
Proc act 04.01 Act val (see page 123). 1073742849
No. Name/Value Description FbEq
Process setpoint × Wake-up level (77.10) / 100
Process actual value
Wake-up delay (77.11)
Time
SLEEPING
Wake-up level (77.10)
Signal selected by 77.09
Wake-up delay (77.11)
Time
SLEEPING
Wake-up level (77.10)
Signal selected by 77.09
Wake-up delay (77.11)
Time
SLEEPING