ValueMains
According to rating label.
Note
For installations according to UL require-
ments, short circuit current rating is 5 kA.
Short circuit current rating
Note
If the controller is to be installed where the specified voltage (see table above)
is not available, the customer is required to provide an external transformer.
Line fusing
As baseline there is no integrated fuse or circuit breaker. The option 3008-3 Mains
connector/Fuse includes integrated circuit breaker.
Current (A)Voltage (V)Robot
3x32 A380 VAC-480 VAC, 3-phaseIRB 460
3x32 A380 VAC-480 VAC, 3-phaseIRB 660
3x16 A380 VAC-480 VAC, 3-phaseIRB 2600
3x32 A380 VAC-480 VAC, 3-phaseIRB 4600
3x32 A380 VAC-480 VAC, 3-phaseIRB 5710
3x32 A380 VAC-480 VAC, 3-phaseIRB 5720
3x32 A380 VAC-480 VAC, 3-phaseIRB 6650S
3x32 A380 VAC-480 VAC, 3-phaseIRB 6660
3x32 A380 VAC-480 VAC, 3-phaseIRB 6700
3x32 A380 VAC-480 VAC, 3-phaseIRB 6710
3x32 A380 VAC-480 VAC, 3-phaseIRB 6720
3x32 A380 VAC-480 VAC, 3-phaseIRB 6730
3x32 A380 VAC-480 VAC, 3-phaseIRB 6740
Note
For details about installations according to UL requirements, see Connecting
incoming mains and protective earth to the controller on page 84.
Residual current
An external earth fault protection (residual current device, RCD) is required. For
detailed information on how to select an external earth fault protection, see
Connecting incoming mains and protective earth to the controller on page 84.
Note
The integrator is responsible to address local electrical requirements.
Continues on next page
Product manual - OmniCore V250XT Type B 41
3HAC087112-001 Revision: A
© Copyright 2023-2023 ABB. All rights reserved.