Parameters 113
Insulation resistance
status
3
MV breaker status 4
Contactor control
duplication
5
Other See Terms and abbreviations on page 57. -
176.12 Spare RO2 source Selects source for setting the state of spare relay
output 2.
Not
connected/
List
Not connected 0
Connected 1
Grounding status 2
Insulation resistance
status
3
MV breaker status 4
Contactor control
duplication
5
Other See Terms and abbreviations on page 57. -
176.21 External fault 1 source Selects source for customer IO external fault 1 signal.
See also MV station monitoring and control on page 50.
Off/
List
Off 0
On 1
Digital input X20.1 2
Digital input X20.2 3
Digital input X20.3 4
Digital input X20.4 5
Digital input X20.5 6
Digital input X20.6 7
Digital input X20.7 8
Spare DI8 9
Spare DI9 10
Spare DI10 11
Spare DI11 12
Spare DI12 13
Other See Terms and abbreviations on page 57. -
176.22 External fault 1 action Selects action type in the event of customer IO external
fault 1.
No action/
List
No action 0
Delayed warning 1
Warning and delayed
fault
2
Delayed fault 3
176.23 External fault 1 action
delay
Defines delay time for customer IO external fault 1
action.
0 s/ List
0...3600 s 1 = 1 s
No. Name/Value Description Def/
FbEq16/32