Troubleshooting 167
44567
(0xae1
7)
PU communication Communication error detected
between control unit and power
unit.
Check that communication
cables are correctly fixed in the
communication unit.
If warning persists, contact your
local FIMER representative.
44569
(0xae1
9)
Measurement circuit
temperature
Problem with internal temperature
measurement of inverter.
Contact your local FIMER
representative.
44570
(0xae1
a)
PU board powerfail Power unit power supply failure Contact your local FIMER
representative.
44577
(0xae2
1)
Flash erase speed
exceeded
Inverter FW not working in optimal
way.
Contact your local FIMER
representative.
44581
(0xae2
5)
FBA A parameter
conflict
Settings in parameter groups 150
FBA and 151 FBA A settings are
configured wrongly.
Reboot the system. If problem
persists contact you local
FIMER representative.
44582
(0xae2
6)
FBA B Parameter
conflict
Settings in parameter groups 150
FBA and 154 FBA B settings are
configured wrongly.
1. Check settings in parameter
groups 150 FBA and 154
FBA B settings. See fieldbus
adapter manual.
2. After making necessary
changes refresh the setting
with parameter 154.27 FBA
par refresh.
44592
(0xae3
0)
FBA A communication Communication lost between BCU
and fieldbus adapter or external
master and fieldbus adapter.
Reboot system. If problem
persists contact you local
FIMER representative.
44593
(0xae3
1)
FBA B communication Communication lost between BCU
and fieldbus adapter or external
master and fieldbus adapter.
Check
status of fieldbus
communication. See user
documentation of fieldbus
interface.
settings of parameter groups
150 FBA, 154 FBA B
settings, 155 FBA B data in
and 156 FBA B data out.
cable connections
the communication of master.
44606
(0xae3
e)
Panel loss Control panel or PC tool has
stopped communicating.
1. Check PC tool or control
panel connection.
2. Check control panel
connector.
3. Replace control panel in
mounting platform.
44631
(0xae5
7)
Autoreset A fault is about to be autoreset.
This is an informative warning.
Code Warning Cause What to do