Troubleshooting 169
57601
(0xe10
1)
Over temperature Over temperature warning level
exceeded. Nominal output current
may not be available.
Aux. code:
1 = indicates temperature
exceeded warning limit in
control section
2 = indicates temperature
exceeded warning limit in power
section
3 = indicates temperature
exceeded warning limit in LCL
section
4 = indicates temperature
exceeded warning limit in IGBT
module
Check aux. code.
Contact your local FIMER
representative.
57603
(0xe10
3)
Excess humidity The relative humidity of cabinet
has exceeded the warning level
regardless of humidity control
attempt.
Aux.code:
1 = indicates excess humidity in
control section
2 = indicates excess humidity in
power section
Humidity level is too high. Wait
for the inverter humidity to rise,
57604
(0xe10
4)
Grounding current
sudden change
Sudden change in grounding
current is detected.
External conditions changed,
that is grounding impedance.
57605
(0xe10
5)
Residual current Residual current warning External conditions changed,
that is, grounding impedance.
Check parameters
210.13...210.17.
Note: Parameter 210.13 is
visible only with Expert level
access.
57606
(0xe10
6)
Grounding circuit over
voltage
MGND internal fuse is blown out. 1. Check MGND card
condition. Internal fuse
broken.
2. Replace MGND card.
57607
(0xe10
7)
Insulation resistance Insulation resistance below limit External conditions changed,
that is grounding impedance.
Check parameters .
57608
(0xe10
8)
Module 1 main air
channel fan fail
A fan failure is detected in at least
one of the main air channel fans in
module 1 (M1).
Contact your local FIMER
representative.
57609
(0xe10
9)
Module 2 main air
channel fan fail
A fan failure is detected in at least
one of the main air channel fans in
module 2 (M2).
Contact your local FIMER
representative.
57612
(0xe10
c)
Module 1 LCL fan fail A fan failure is detected in at least
one of the LCL fans in module 1
(M1).
Contact your local FIMER
representative.