170 Troubleshooting
57613
(0xe10
d)
Module 2 LCL fan fail A fan failure is detected in at least
one of the LCL fans in module 2
(M2).
Contact your local FIMER
representative.
57616
(0xe11
0)
Fan status feedback
M1
Module 1 internal cabinet fan
failure.
Contact your local FIMER
representative.
57617
(0xe11
1)
Fan status feedback
M2
Module 2 internal cabinet fan
failure.
Contact your local FIMER
representative.
57620
(0xe11
4)
Temperature sensor
fail
Temperature sensor failure
detected. At least one of
temperature measurements has
exceeded sanity check limits.
Check status parameter of
failed temperature sensor with
parameter 211.71 Sensor fail
status.
57622
(0xe11
6)
PLC manual test mode
active
PLC manual test mode is active.
Normal inverter operation is not
possible.
Check parameter 209.01 PLC
manual test mode.
57623
(0xe11
7)
Hot ambient
temperature
The maximum operational ambient
temperature is exceeded.
Inverter operation may be
inhibited.
Wait for ambient temperature to
increase.
57624
(0xe11
8)
Cold ambient
temperature
The minimum operational ambient
temperature deceeded.
Inverter operation may be
inhibited.
Wait for ambient temperature to
increase.
57625
(0xe11
9)
Option code not
defined
Option code is not yet defined.
Inverter start inhibited.
Check that parameters
206.101...120 is not set to “Not
defined”. Select correct module
manually.
57626
(0xe11
a)
Wrong PLC HW
configuration
PLC hardware and set option
codes do not match.
Aux code 1: configuration code is
not set.
• Check that parameters
206.102 and 206.103 are set
according to the inverter
nameplate option codes.
• Reboot the inverter.
• If problem persists, contact
your local FIMER
representative.
57627
(0xe11
b)
DC voltage not stable
for starting
DC voltage oscillation during start
sequence. DC voltage has not
stabilized to open circuit voltage
and inverter start up failed.
Check DC input voltage with
parameter 208.01 Input voltage.
Try to disable and enable the
inverter with parameter 189.01
Inverter operation. If problem
persists, contact FIMER.
Note: Parameter 208.01 is
visible only with Expert level
access.
57628
(0xe11
c)
Night Q feature not
supported
Night Q mode is not supported in
this inverter.
Contact your local FIMER
representative.
Code Warning Cause What to do