174 Troubleshooting
57668
(0xe14
4)
Disabling all modules
requested
All modules are requested to be
disabled.
Enable at least one module for
operating system.
57669
(0xe14
5)
Disabling non-existing
module
A module not existing in
configuration is requested to be
disabled.
Check module disable forcing
parameters.
57671
(0xe14
7)
Heating CB or aux
SPD
Heating circuit breaker or auxiliary
SPD failed because auxiliary
circuit breaker monitoring signal is
down but 48 V power supply status
is OK.
See aux. code for module
information.
57672
(0xe14
8)
PLC version not
supported
PLC software version is not
supported.
Update PLC software version.
57680
(0xe15
0)
Transfer trip Transfer trip command received. Remove command.
57681
(0xe15
1)
Shutdown Shut down command received
from digital input or SCADA.
Remove command.
57682
(0xe15
2)
DC input configuration DC input is connected even
though it is not configured as
connected.
Aux. code (format XY):
X = indicates faulty module
number
Y = indicates faulty DC input
number.
Check aux. code.
Check M1...M4 connected
DC inputs from parameter
group 174 DC input current
monitor.
57683
(0xe15
3)
DC input current
deviation
Current deviation detected.
Aux. code (format XY):
X = indicates faulty module
number
Y = indicates faulty DC input
number.
Check aux. code.
Examine affected DC input
for shading.
Make sure panels in affected
DC inputs are not damaged.
Make sure DC input
monitoring configuration
settings are feasible.
57684
(0xe15
4)
Blown DC input fuse Blown DC input fuse detected.
Aux. code (format XY):
X = indicates faulty module
number
Y = indicates faulty DC input
number.
Check aux. code.
If warning persists, contact your
local FIMER representative to
replace failed DC input fuses.